Quantification of interface-charge-induced electric-field distortion in multi-oil-gap oil–pressboard insulation under DC voltage

Chunjia Gao, Xiangsong Meng, Peng Zhang, Xiaolin Zhao, Deshen Li, Bo Qi, Chengrong Li

Journal of Physics D: Applied Physics · 19.06.2026 · 59 (24) · 245501

DOI: 10.1088/1361-6463/ae757f ↗

Kurz gefasst

Fachartikel in der Zeitschrift Journal of Physics D: Applied Physics, online erschienen am 17.06.2026. Verfasst von Chunjia Gao und 6 weiteren Autor:innen. Die Arbeit nennt 25 Literaturangaben. Gefördert von: National Key R&D Program of China.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

The internal insulation of ultra-high-voltage converter transformers usually consists of alternating oil gaps and oil-impregnated pressboards, in which interface charge accumulation may distort the DC electric field. However, most existing studies have focused on single- or double-layer structures, and the electric-field distribution in multi-oil-gap insulation remains insufficiently understood. An interface-charge measurement platform based on the Kerr electro-optic effect and AC modulation was developed to investigate double-oil-gap and five-oil-gap oil–pressboard models. The results obtained from the double-oil-gap models show that the conventional polarity-dependent charge accumulation behavior does not fully account for the measured field distribution when the adjacent oil-gap ratio reaches 3:1 at an oil-field strength above 1.00 kV mm −1 , or exceeds 5:1 at an oil-field strength above 0.55 kV mm −1 . Under these conditions, the electric field in the upper and lower oil gaps exhibits a clear inversion. Measurements on the five-oil-gap model further reveal a non-uniform field distribution. For both voltage polarities, the field strength is highest in gap #1, decreases from gap #1 to gap #4, and then increases again in gap #5. Under +40 kV, the field rises from 0.21–0.22 kV mm −1 in gap #4–0.37–0.39 kV mm −1 in gap #5; under −40 kV, it increases from 0.20–0.21 kV mm −1 to 0.33–0.34 kV mm −1 . To quantify the corresponding interface charge distribution, a multi-interface charge calculation method based on the superposition integral and matrix formulation is proposed. The inversely calculated electric-field profiles are consistent with the measured values, with relative errors ranging from 4.8% to 14.3%. These results provide an experimental and computational basis for evaluating charge-induced electric-field distortion and verifying insulation margins in multi-layer oil–pressboard insulation under DC voltage.

Förderung

  • National Key R&D Program of China

Zitieren

APA

Gao, C., Meng, X., Zhang, P., Zhao, X., Li, D., Qi, B., & Li, C. (2026). Quantification of interface-charge-induced electric-field distortion in multi-oil-gap oil–pressboard insulation under DC voltage. Journal of Physics D: Applied Physics, 59(24), 245501. https://doi.org/10.1088/1361-6463/ae757f

Vancouver

Gao C, Meng X, Zhang P, Zhao X, Li D, Qi B, et al. Quantification of interface-charge-induced electric-field distortion in multi-oil-gap oil–pressboard insulation under DC voltage. Journal of Physics D: Applied Physics. 2026;59(24):245501. doi:10.1088/1361-6463/ae757f

BibTeX
@article{Gao2026,
  author = {Gao, Chunjia and Meng, Xiangsong and Zhang, Peng and Zhao, Xiaolin and Li, Deshen and Qi, Bo and Li, Chengrong},
  title = {Quantification of interface-charge-induced electric-field distortion in multi-oil-gap oil–pressboard insulation under DC voltage},
  journal = {Journal of Physics D: Applied Physics},
  year = {2026},
  volume = {59},
  number = {24},
  pages = {245501},
  doi = {10.1088/1361-6463/ae757f}
}
Kostenlos starten →