Evaluation of Airborne Particulates and Fungi During Hospital Renovation
American Industrial Hygiene Association Journal · 1995-07 · 56 (7) · 706-712
DOI: 10.1080/15428119591016737 ↗Kurz gefasst
Fachartikel in der Zeitschrift American Industrial Hygiene Association Journal, online erschienen am 04.06.2010. Verfasst von P A Overberger und 2 weiteren Autor:innen. Beteiligte Einrichtung: University of Pittsburgh Graduate School of Public Health, Department of Infectious Diseases and Microbiology, PA 15261, USA. Hauptthemen laut MEDLINE: Air Microbiology, Air Pollution, Indoor, Fungi, Hospital Design and Construction. Die Arbeit wurde bisher 25-mal zitiert (Crossref).
Abstract (Originalsprache)
This study was conducted over 30 weeks on a hospital floor undergoing partial renovation. Some patients housed on the floor were immunosuppressed, including bone marrow transplant recipients. The construction zone was placed under negative pressure and was separated from patient rooms by existing hospital walls and via erection of a temporary barrier. Other control measures minimized patient exposure to airborne materials. Air sampling was done for 3 weeks prior to construction, 24 weeks during construction, and 3 weeks after renovation was completed. Airborne particulate concentrations, total spore counts, particle size, and fungal species were assessed. At the beginning of the renovation there were increases in airborne particulates (from 0.2 to 2.0 mg/m3) and fungal spores (from 3.5 to 350 colony forming units (CFU/m3), but only in the construction zone. Throughout the remainder of the renovation, particulate and fungal spore levels fluctuated inside the construction zone but remained close to baseline values in the patient area. When renovation was completed, particulates and spore counts inside the construction zone decreased to preconstruction levels. The primary fungus isolated from air samples was Penicillium. This study demonstrated that control measures were effective in reducing exposures of hospitalized patients to airborne particulates and spores and in reducing the increased risk of aspergillosis and other fungal infections associated with hospital construction projects. The data from this study may be useful in establishing exposure guidelines for other health care settings.
Schlagwörter
MeSH-Schlagwörter (MEDLINE)
Autor:innen und Institutionen
- University of Pittsburgh Graduate School of Public Health, Department of Infectious Diseases and Microbiology, PA 15261, USA.
Zitieren
APA
Overberger, P. A., Wadowsky, R. M., & Schaper, M. M. (1995). Evaluation of Airborne Particulates and Fungi During Hospital Renovation. American Industrial Hygiene Association Journal, 56(7), 706-712. https://doi.org/10.1080/15428119591016737
Vancouver
Overberger PA, Wadowsky RM, Schaper MM. Evaluation of Airborne Particulates and Fungi During Hospital Renovation. American Industrial Hygiene Association Journal. 1995;56(7):706-712. doi:10.1080/15428119591016737
BibTeX
@article{Overberger1995,
author = {Overberger, P A and Wadowsky, R M and Schaper, M M},
title = {Evaluation of Airborne Particulates and Fungi During Hospital Renovation},
journal = {American Industrial Hygiene Association Journal},
year = {1995},
volume = {56},
number = {7},
pages = {706--712},
doi = {10.1080/15428119591016737}
}
EUVIMED