Live-line impulse voltage detection of internal defects in porcelain insulators: An alternative to insulation resistance measurement

Lu Wen iD, Daiming Yang iD, Liming Wang iD, Bin Cao iD

Review of Scientific Instruments · 01.11.2026 · 97 (11)

DOI: 10.1063/5.0353235 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Review of Scientific Instruments, online erschienen am 16.11.2026. Verfasst von Lu Wen und 3 weiteren Autor:innen. Beteiligte Einrichtung: Tsinghua Shenzhen International Graduate School, Institute of Advanced Technologies in Energy and Electrical Engineering, Shenzhen, China. Die Arbeit nennt 24 Literaturangaben. Gefördert von: Basic and Applied Basic Research Foundation of Guangdong Province.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Conventional detection methods for internal defects in porcelain insulators rely on the premise that such defects invariably reduce insulation resistance. Through controlled water-penetration experiments, this study reveals that the cement layer and dry cracks can mask defects, preserving high insulation resistance and causing conventional techniques to fail. We developed an impulse-voltage device that directly interrogates dielectric integrity by applying a high-voltage impulse. Comprehensive offline tests on insulators of various mechanical strengths confirm that defective units exhibit significantly lower impulse amplitudes than defect-free units, establishing a clear diagnostic threshold. Crucially, the method demonstrates robust performance under live-line conditions: validation tests under both AC and DC energization, as well as across a wide humidity range (up to 90% RH), confirm that the diagnostic criterion remains valid without de-energizing the line. This live-line capability, combined with its resilience to surface leakage, offers a practical, field-deployable alternative to conventional insulation-resistance approaches and is currently being integrated onto a robotic platform for automated inspection.

Autor:innen und Institutionen

  • Tsinghua Shenzhen International Graduate School, Institute of Advanced Technologies in Energy and Electrical Engineering, Shenzhen, China.
  • School of Mechanical and Electrical Engineering, Shenzhen Polytechnic University, Shenzhen, China.

ORCID-Profile: Lu Wen, Daiming Yang, Liming Wang, Bin Cao

Förderung

  • Basic and Applied Basic Research Foundation of Guangdong Province

Zitieren

APA

Wen, L., Yang, D., Wang, L., & Cao, B. (2026). Live-line impulse voltage detection of internal defects in porcelain insulators: An alternative to insulation resistance measurement. Review of Scientific Instruments, 97(11). https://doi.org/10.1063/5.0353235

Vancouver

Wen L, Yang D, Wang L, Cao B. Live-line impulse voltage detection of internal defects in porcelain insulators: An alternative to insulation resistance measurement. Review of Scientific Instruments. 2026;97(11). doi:10.1063/5.0353235

BibTeX
@article{Wen2026,
  author = {Wen, Lu and Yang, Daiming and Wang, Liming and Cao, Bin},
  title = {Live-line impulse voltage detection of internal defects in porcelain insulators: An alternative to insulation resistance measurement},
  journal = {Review of Scientific Instruments},
  year = {2026},
  volume = {97},
  number = {11},
  doi = {10.1063/5.0353235}
}
Kostenlos starten →