Investigation on vacuum arc characteristics and anode temperature of 16.7 Hz vacuum interruption
AIP Advances · 01.07.2026 · 16 (7)
DOI: 10.1063/5.0335392 ↗Kurz gefasst
Fachartikel in der Zeitschrift AIP Advances, online erschienen am 23.07.2026. Verfasst von Jun Xiong und 7 weiteren Autor:innen. Die Arbeit nennt 26 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).
Abstract (Originalsprache)
Low-frequency vacuum circuit breakers exhibit longer arcing durations during contact separation compared to power frequency currents, due to the lower frequency of the interrupted AC arc. This extended arcing time intensifies contact ablation, reducing the breaker’s interruption capability and operational lifespan. This study employs modeling and simulation to establish a three-dimensional magnetohydrodynamic model based on a uniform axial magnetic field. The model investigates three distinct vacuum arcing processes interrupted at different half-wave instants under 16.7 Hz current conditions, aiming to elucidate the transport properties of the low-frequency vacuum arc plasma and its underlying regulation mechanisms. By calculating key plasma transport properties (ion temperature, plasma pressure, ion velocity, ion number density, and current density), the energy flux density injected from the arc column toward the anode during the interruption process is determined. This calculated energy flux density serves as a boundary condition for simulating the temporal evolution of anode temperature during interruption. Results indicate that arc interruption at the current zero-crossing point yields a more uniform and relatively lower temperature distribution on the anode contact. The findings of this study provide insights into the interelectrode physical processes and anode conditions of vacuum circuit breakers during low-frequency operation under varying interruption instants. Furthermore, they provide references for optimized design to enhance the interruption capability and extend the operational lifespan of low-frequency circuit breakers.
Zitieren
APA
Xiong, J., Hong, H., Zhou, X., Liu, J., Su, H., Xiao, J., Huang, X., & Jia, S. (2026). Investigation on vacuum arc characteristics and anode temperature of 16.7 Hz vacuum interruption. AIP Advances, 16(7). https://doi.org/10.1063/5.0335392
Vancouver
Xiong J, Hong H, Zhou X, Liu J, Su H, Xiao J, et al. Investigation on vacuum arc characteristics and anode temperature of 16.7 Hz vacuum interruption. AIP Advances. 2026;16(7). doi:10.1063/5.0335392
BibTeX
@article{Xiong2026,
author = {Xiong, Jun and Hong, Haicheng and Zhou, Xihao and Liu, Junxiang and Su, Haibo and Xiao, Jun and Huang, Xiaolong and Jia, Shenli},
title = {Investigation on vacuum arc characteristics and anode temperature of 16.7 Hz vacuum interruption},
journal = {AIP Advances},
year = {2026},
volume = {16},
number = {7},
doi = {10.1063/5.0335392}
}