EUVIMEDEUVIMED entdecken
Open Access · CC BY-NC-ND 4.0

Numerical simulation on fault arc characteristics of medium voltage air medium switchgear

Lijun Wang, Xinyi Liu, Kexiang Huang, Tongqi Liu, Xuanrui Zhang

AIP Advances · 01.11.2025 · 15 (11)

DOI: 10.1063/5.0293975 ↗

Kurz gefasst

Fachartikel in der Zeitschrift AIP Advances, online erschienen am 11.11.2025. Verfasst von Lijun Wang und 4 weiteren Autor:innen. Die Arbeit wurde bisher 2-mal zitiert (Crossref) und nennt 32 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY-NC-ND 4.0). Gefördert von: National Natural Science Foundation of China.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Based on magnetohydrodynamic theory, this paper establishes a two-dimensional axisymmetric model of a fault arc inside an enclosed medium-voltage (MV) air-insulated switchgear. Using COMSOL Multiphysics, the Navier–Stokes and Maxwell equations are coupled to simulate the temperature field, gas flow field, arc energy, and arc voltage. The results illustrate the temperature distribution and pressure variation during the arc burning process. Arc temperature is found to be proportional to the current variation. During unstable burning, arc movement direction changes. The gas flow velocity depends on the volume force acting on it; a greater resultant force from the pressure gradient and Lorentz force leads to a higher arc velocity. Pressure measurements at the arc center and chamber wall indicate a continuous pressure rise during arc burning, culminating in an increase of ∼350 kPa. Under unstable arc conditions, the arc voltage and energy oscillate and deviate from proportionality to the current. These findings provide practical implications for arc fault management and enclosure design in MV switchgear systems.

Förderung

  • National Natural Science Foundation of China

Zitieren

APA

Wang, L., Liu, X., Huang, K., Liu, T., & Zhang, X. (2025). Numerical simulation on fault arc characteristics of medium voltage air medium switchgear. AIP Advances, 15(11). https://doi.org/10.1063/5.0293975

Vancouver

Wang L, Liu X, Huang K, Liu T, Zhang X. Numerical simulation on fault arc characteristics of medium voltage air medium switchgear. AIP Advances. 2025;15(11). doi:10.1063/5.0293975

BibTeX
@article{Wang2025,
  author = {Wang, Lijun and Liu, Xinyi and Huang, Kexiang and Liu, Tongqi and Zhang, Xuanrui},
  title = {Numerical simulation on fault arc characteristics of medium voltage air medium switchgear},
  journal = {AIP Advances},
  year = {2025},
  volume = {15},
  number = {11},
  doi = {10.1063/5.0293975}
}