Active on-site calibration technology of current transformer based on non-rated frequency current injection

Xin Qi, Baoquan Wan, Jun Zhang, Quan Wang, Haibin Chen, Qiancheng Zhao, Binwu Wang

Review of Scientific Instruments · 01.07.2024 · 95 (7)

DOI: 10.1063/5.0209242 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Review of Scientific Instruments, online erschienen am 10.07.2024. Verfasst von Xin Qi und 6 weiteren Autor:innen. Beteiligte Einrichtung: China Electric Power Research Institute, Wuhan 430074, China. Die Arbeit wurde bisher 4-mal zitiert (Crossref) und nennt 21 Literaturangaben.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

This paper proposes an active on-site calibration method through background current cancellation and non-rated current injection. It can measure the error of the current transformer in service from 1% to 120% rated current percentage without power supply interruption. In order to establish the error relationship between rated frequency and arbitrary frequency, a theoretical analysis of current transformer calibration at the arbitrary frequency has been developed by means of the equivalent circuit. It describes a method to determine the phase angle and ratio errors of the measuring transformers at arbitrary frequencies on the basis of the calibrated error values at rated frequency. To prove the theoretical analysis, an experimental validation was carried out. The experimental results demonstrate that this active onsite calibration is a valid tool for the evaluation of current transformer performances. The calibration results showed that, for both cases (non-rated frequency calibration and mixing frequency calibration), the difference between mean ratio error and rated frequency ratio error was lower than 0.01%, and the difference between mean phase error and rated frequency phase error was lower than 1′, which meets the requirement of the 0.2 accuracy class calibration.

Autor:innen und Institutionen

  • China Electric Power Research Institute, Wuhan 430074, China.
  • State Grid Shanghai Municipal Electric Power Company, Shanghai 200050, China.

Zitieren

APA

Qi, X., Wan, B., Zhang, J., Wang, Q., Chen, H., Zhao, Q., & Wang, B. (2024). Active on-site calibration technology of current transformer based on non-rated frequency current injection. Review of Scientific Instruments, 95(7). https://doi.org/10.1063/5.0209242

Vancouver

Qi X, Wan B, Zhang J, Wang Q, Chen H, Zhao Q, et al. Active on-site calibration technology of current transformer based on non-rated frequency current injection. Review of Scientific Instruments. 2024;95(7). doi:10.1063/5.0209242

BibTeX
@article{Qi2024,
  author = {Qi, Xin and Wan, Baoquan and Zhang, Jun and Wang, Quan and Chen, Haibin and Zhao, Qiancheng and Wang, Binwu},
  title = {Active on-site calibration technology of current transformer based on non-rated frequency current injection},
  journal = {Review of Scientific Instruments},
  year = {2024},
  volume = {95},
  number = {7},
  doi = {10.1063/5.0209242}
}
Kostenlos starten →