Kurz gefasst

Fachartikel in der Zeitschrift IET Smart Grid, online erschienen am 27.02.2026. Verfasst von Anas AlMajali und 4 weiteren Autor:innen. Die Arbeit wurde bisher 1-mal zitiert (Crossref) und nennt 23 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Load tap changers (LTCs) play a critical role in voltage regulation, and their manipulation creates serious risks for distribution system stability. In this work, a digital model of a realistic power grid was utilised to investigate coordinated cyberphysical attacks, where LTC tap ratios were set to extreme values in parallel with selective customer load changes. The analysis shows that although the main bus often remained close to nominal conditions, feeder buses deviated significantly, with voltages dropping to 0.75 p.u. in undervoltage cases and rising beyond 1.07 p.u. when the LTC was forced upward. Photovoltaic (PV) integration modified these outcomes. During undervoltage scenarios, PV injection increased bus voltages by 0.02–0.03 p.u., improving stability margins. In contrast, under overvoltage conditions, PV generation exacerbated the rise, with feeders approaching 1.10 p.u. Load shedding was also examined; it reduced undervoltage deviations but further elevated voltages during overvoltage, highlighting its asymmetric effectiveness. This study contributes to understanding by demonstrating how the coordinated manipulation of LTC operation and load can drive system‐wide voltage instability, even when appearing normal at central monitoring points. It also clarifies the dual role of PV under attack conditions and emphasises that conventional countermeasures are insufficient. A layered defence approach, combining secure LTC communication, feeder‐level anomaly detection and adaptive voltage support, is essential for maintaining resilience in renewable‐integrated distribution networks.

Zitieren

APA

AlMajali, A., Alasali, F., El‐Naily, N., Abuashour, M. I., & Ghalyon, S. A. (2026). Impact of Cyberphysical Attacks on Load Tap Changers and Distribution System Voltage Stability. IET Smart Grid, 9(1). https://doi.org/10.1049/stg2.70076

Vancouver

AlMajali A, Alasali F, El‐Naily N, Abuashour MI, Ghalyon SA. Impact of Cyberphysical Attacks on Load Tap Changers and Distribution System Voltage Stability. IET Smart Grid. 2026;9(1). doi:10.1049/stg2.70076

BibTeX
@article{AlMajali2026,
  author = {AlMajali, Anas and Alasali, Feras and El‐Naily, Naser and Abuashour, Mohammed I. and Ghalyon, Salah Abu},
  title = {Impact of Cyberphysical Attacks on Load Tap Changers and Distribution System Voltage Stability},