Experimental Comparison of Optical Detection Performance for Partial Discharge in GIS: PMT, Fluorescent Fiber and SiPM
IET Science, Measurement & Technology · 2026-01 · 20 (1)
DOI: 10.1049/smt2.70085 ↗Kurz gefasst
Fachartikel in der Zeitschrift IET Science, Measurement & Technology, online erschienen am 23.08.2026. Verfasst von Wei Wang und 5 weiteren Autor:innen. Die Arbeit nennt 18 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY-NC-ND 4.0).
Abstract (Originalsprache)
Addressing the challenges of high miss rates and poor field applicability in partial discharge (PD) detection for ultra‐high voltage gas insulated switchgear (GIS), this paper compares the characteristics of three mainstream PD detection systems. Firstly, we constructed five typical discharge defect models—point contact, particle, tracking, air gap and suspension on the same 110 kV single‐phase GIS platform. Subsequently, optical detection systems employing photomultiplier tubes (PMT), fluorescent optical fibers (FOF) and silicon photomultiplier tubes (SiPM) were employed to measure PD signals. Secondly, using pulse repetition rate (PRR) and average pulse amplitude (APA) as evaluation metrics, the sensitivity and effective detection range of each approach were quantified. Results indicate that PMTs exhibit superior sensitivity and fault detection rates compared to other optical discharge detection systems. Under identical experimental conditions, PMTs reduce the detection threshold to below 10 pC and maintain a >90% detection probability at 1500 mm for 150 pC discharges, significantly outperforming FOFs and SiPMs. This study provides selection principles and optimization directions for the three technical approaches in scenarios involving long‐distance, low‐discharge‐level ultra‐high‐voltage GIS, offering an experimental basis for the engineering application of optical detection methods.
Zitieren
APA
Wang, W., Wang, Q., Wang, X., Yang, Z., Wang, S., & Gao, K. (2026). Experimental Comparison of Optical Detection Performance for Partial Discharge in GIS: PMT, Fluorescent Fiber and SiPM. IET Science, Measurement & Technology, 20(1). https://doi.org/10.1049/smt2.70085
Vancouver
Wang W, Wang Q, Wang X, Yang Z, Wang S, Gao K. Experimental Comparison of Optical Detection Performance for Partial Discharge in GIS: PMT, Fluorescent Fiber and SiPM. IET Science, Measurement & Technology. 2026;20(1). doi:10.1049/smt2.70085
BibTeX
@article{Wang2026,
author = {Wang, Wei and Wang, Qilin and Wang, Xiaohui and Yang, Zhifei and Wang, Shenghui and Gao, Ke},
title = {Experimental Comparison of Optical Detection Performance for Partial Discharge in GIS: PMT, Fluorescent Fiber and SiPM},
journal = {IET Science, Measurement & Technology},
year = {2026},
volume = {20},
number = {1},
doi = {10.1049/smt2.70085}
}
EUVIMED