Improved design of passive damping for single phase grid‐connected LCL filtered inverter considering impedance stability

Ramy Ali, Hamed Heydari‐doostabad, Shahab Sajedi, Terence O'Donnell

IET Power Electronics · 2024-03 · 17 (4) · 511-523

DOI: 10.1049/pel2.12666 ↗

Kurz gefasst

Fachartikel in der Zeitschrift IET Power Electronics, online erschienen am 07.02.2024. Verfasst von Ramy Ali und 3 weiteren Autor:innen. Die Arbeit wurde bisher 14-mal zitiert (Crossref) und nennt 46 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Science Foundation Ireland.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Grid‐connected inverters with an inductor–capacitor–inductor (LCL) filter usually require the implementation of damping in the filter to suppress the resonance associated with the filter and hence ensure internal stability. The value for the damping resistor is commonly chosen as one‐third of the capacitive reactance at the resonance frequency of the LCL filter. However, this commonly‐used principle does not take into account the external stability of the inverter, i.e. the potential for an interaction between the inverter output impedance and the grid impedance. This work discusses a new design for the damping resistor to assure the external stability of the voltage source inverter as well as its internal stability. The analysis shows that the proposed design can ensure the external stability of the voltage source inverter with different grid impedances as well as robustness against the variations of the filter parameters while maintaining low power losses and an acceptable attenuation rate for high‐frequency harmonics. To validate the theoretical analysis, a 1 kW, 110 V laboratory prototype is implemented. The obtained results confirm the applicability of the proposed design approach.

Förderung

  • Science Foundation Ireland

Zitieren

APA

Ali, R., Heydari‐doostabad, H., Sajedi, S., & O'Donnell, T. (2024). Improved design of passive damping for single phase grid‐connected LCL filtered inverter considering impedance stability. IET Power Electronics, 17(4), 511-523. https://doi.org/10.1049/pel2.12666

Vancouver

Ali R, Heydari‐doostabad H, Sajedi S, O'Donnell T. Improved design of passive damping for single phase grid‐connected LCL filtered inverter considering impedance stability. IET Power Electronics. 2024;17(4):511-523. doi:10.1049/pel2.12666

BibTeX
@article{Ali2024,
  author = {Ali, Ramy and Heydari‐doostabad, Hamed and Sajedi, Shahab and O'Donnell, Terence},
  title = {Improved design of passive damping for single phase grid‐connected LCL filtered inverter considering impedance stability},
  journal = {IET Power Electronics},
  year = {2024},
  volume = {17},
  number = {4},
  pages = {511--523},
  doi = {10.1049/pel2.12666}
}
Kostenlos starten →