EUVIMEDEUVIMED entdecken
Open Access · CC BY-NC-ND 4.0

A novel GIS breakdown location method based on natural frequency of transient voltage

Qiang Sun, Dengwei Ding, Yanpeng Ge, Ziwei Zhang, Wensheng Gao, Weidong Liu, Ke Zhao, Bo Liu, Lei Wang, Jiaqi Qu

High Voltage · 2025-08 · 10 (4) · 856-875

DOI: 10.1049/hve2.70079 ↗

Kurz gefasst

Fachartikel in der Zeitschrift High Voltage, online erschienen am 18.08.2025. Verfasst von Qiang Sun und 9 weiteren Autor:innen. Die Arbeit wurde bisher 2-mal zitiert (Crossref) und nennt 43 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY-NC-ND 4.0).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

During on‐site withstand voltage tests of gas‐insulated switchgears (GIS), once a breakdown occurs, it is hard to locate the breakdown position due to the intricate branch structures and minimal breakdown energy. The existing methods may require the placement of a large number of sensors with unsatisfactory accuracy, which adversely affects the process of inspecting and repairing, as well as the subsequent tests. To address this issue, this paper introduces a novel GIS breakdown location method. This method is predicated on the natural frequency of the transient voltage caused by the breakdown. The relationship between the breakdown position and the natural frequency is first derived, which is referred to as the location equation. Then, the natural frequency characteristics are discussed from both mathematical and energy perspectives. Based on these characteristics, the location method is proposed that utilises the location equation and the frequencies at two measurement points. The results of the laboratory experiments demonstrate the accuracy of the method and certain advantages over the ultrasonic method. Further, the effectiveness of the method in GIS and gas‐insulated transmission lines (GIL) with complex structures and high voltage levels is also confirmed by simulation cases and field experimental data.

Zitieren

APA

Sun, Q., Ding, D., Ge, Y., Zhang, Z., Gao, W., Liu, W., Zhao, K., Liu, B., Wang, L., & Qu, J. (2025). A novel GIS breakdown location method based on natural frequency of transient voltage. High Voltage, 10(4), 856-875. https://doi.org/10.1049/hve2.70079

Vancouver

Sun Q, Ding D, Ge Y, Zhang Z, Gao W, Liu W, et al. A novel GIS breakdown location method based on natural frequency of transient voltage. High Voltage. 2025;10(4):856-875. doi:10.1049/hve2.70079

BibTeX
@article{Sun2025,
  author = {Sun, Qiang and Ding, Dengwei and Ge, Yanpeng and Zhang, Ziwei and Gao, Wensheng and Liu, Weidong and Zhao, Ke and Liu, Bo and Wang, Lei and Qu, Jiaqi},
  title = {A novel GIS breakdown location method based on natural frequency of transient voltage},
  journal = {High Voltage},
  year = {2025},
  volume = {10},
  number = {4},
  pages = {856--875},
  doi = {10.1049/hve2.70079}
}
Kostenlos starten →