Thermal runaway and induced electrical failure of epoxy resin in high‐frequency transformers: Insulation design reference
High Voltage · 2024-10 · 9 (5) · 989-1000
DOI: 10.1049/hve2.12424 ↗Kurz gefasst
Fachartikel in der Zeitschrift High Voltage, online erschienen am 11.03.2024. Verfasst von Xingyu Shang und 3 weiteren Autor:innen. Die Arbeit wurde bisher 32-mal zitiert (Crossref) und nennt 29 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY-NC-ND 4.0). Gefördert von: National Natural Science Foundation of China - State Grid Corporation Joint Fund for Smart Grid.
Abstract (Originalsprache)
Solid‐state transformers (SSTs) have applications in medium‐voltage direct current (MVDC) grids and compact power systems. High‐frequency transformer (HFT) is the core component of SSTs. High levels of high frequency high d v /d t voltage stresses challenged the integrity of the galvanic insulation of HFTs. However, dielectric thermal runaway and resultant electrical failure mechanisms in epoxy resin (EP) cast insulation remain unclear. Dielectric heating of EP across varying voltages, frequencies, rising edges, duty cycles and DC biases were measured and corroborated by simulation. The thermal runaway threshold mainly depends on the tangency point of the loss generation and heat dissipation curves below the glass transition temperature. Observations reveal that thermal runaway does not directly cause breakdown; instead, thermal decomposition above 200°C triggers discharge and eventual failure. Simulations demonstrate that temperature rise mainly depends on the average field within the electrode region and inter‐segment and inter‐layer distances within the HFT winding definitively impact insulation thermal runaway. By applying different criteria for MV and high‐voltage (HV) transformers, the reference electric fields for insulation design with unfilled and filled EP were obtained. For instance, limiting dielectric heating below 5 K at 50 kHz necessitates an RMS average field less than 0.44 V/mm, which is much lower than dry‐type transformer conventions. The authors prove the necessity of re‐evaluating the permissible field strength in HFT insulation design.
Förderung
- National Natural Science Foundation of China - State Grid Corporation Joint Fund for Smart Grid
Zitieren
APA
Shang, X., Pang, L., Bu, Q., & Zhang, Q. (2024). Thermal runaway and induced electrical failure of epoxy resin in high‐frequency transformers: Insulation design reference. High Voltage, 9(5), 989-1000. https://doi.org/10.1049/hve2.12424
Vancouver
Shang X, Pang L, Bu Q, Zhang Q. Thermal runaway and induced electrical failure of epoxy resin in high‐frequency transformers: Insulation design reference. High Voltage. 2024;9(5):989-1000. doi:10.1049/hve2.12424
BibTeX
@article{Shang2024,
author = {Shang, Xingyu and Pang, Lei and Bu, Qinhao and Zhang, Qiaogen},
title = {Thermal runaway and induced electrical failure of epoxy resin in high‐frequency transformers: Insulation design reference},
journal = {High Voltage},
year = {2024},
volume = {9},
number = {5},
pages = {989--1000},
doi = {10.1049/hve2.12424}
}