EUVIMEDEUVIMED entdecken
Open Access · CC BY-NC-ND 4.0

Thermofluidic investigations of oil natural transformer: Closed‐loop modelling and experimental validation

Yuan Li, Yiran Gao, Chen Wang, Chao Zhu, Ying Li, Yuankai Wang, Guanjun Zhang

High Voltage · 2024-02 · 9 (1) · 230-240

DOI: 10.1049/hve2.12345 ↗

Kurz gefasst

Fachartikel in der Zeitschrift High Voltage, online erschienen am 20.06.2023. Verfasst von Yuan Li und 6 weiteren Autor:innen. Die Arbeit wurde bisher 17-mal zitiert (Crossref) und nennt 26 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY-NC-ND 4.0).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Excessively high temperatures inside a power transformer can accelerate the ageing rate and even cause unplanned outages. Accurately estimating the hot‐spot temperature (HST) of a power transformer is important for regulating the load and ensuring long‐term operation. In this study, a closed‐loop model of a 110‐kV product transformer with an oil natural/air forced (ONAF) cooling mode is built to predict HST, in which the compression ratio of windings, equivalent heat source and radiator geometry are considered. According to the flow field of the winding, the ‘dead oil zone’ and reverse oil flow are observed in the horizontal oil channels. The accuracy of the proposed model is experimentally validated by temperature‐rise tests. The results show that the absolute errors between the measured results and simulation are below 5°C, and the average error is ∼2°C. Furthermore, the arrangements of windings and radiators are studied to enhance the oil circulation. By adding 5 washers to the high‐voltage winding, the average temperature can be decreased by 6°C compared with the case without a washer. Elevating the radiator can also mitigate the characteristic temperatures, and the optimal height difference between the radiator and winding centre is suggested to be 0.66 m.

Zitieren

APA

Li, Y., Gao, Y., Wang, C., Zhu, C., Li, Y., Wang, Y., & Zhang, G. (2024). Thermofluidic investigations of oil natural transformer: Closed‐loop modelling and experimental validation. High Voltage, 9(1), 230-240. https://doi.org/10.1049/hve2.12345

Vancouver

Li Y, Gao Y, Wang C, Zhu C, Li Y, Wang Y, et al. Thermofluidic investigations of oil natural transformer: Closed‐loop modelling and experimental validation. High Voltage. 2024;9(1):230-240. doi:10.1049/hve2.12345

BibTeX
@article{Li2024,
  author = {Li, Yuan and Gao, Yiran and Wang, Chen and Zhu, Chao and Li, Ying and Wang, Yuankai and Zhang, Guanjun},
  title = {Thermofluidic investigations of oil natural transformer: Closed‐loop modelling and experimental validation},
  journal = {High Voltage},
  year = {2024},
  volume = {9},
  number = {1},
  pages = {230--240},
  doi = {10.1049/hve2.12345}
}
Kostenlos starten →