Three‐phase four‐wire power flow solution for multi‐grounded distribution networks with non‐bolted grounding
IET Generation, Transmission & Distribution · 2024-12 · 18 (23) · 3914-3927
DOI: 10.1049/gtd2.13316 ↗Kurz gefasst
Fachartikel in der Zeitschrift IET Generation, Transmission & Distribution, online erschienen am 11.11.2024. Verfasst von Nien‐Che Yang und 1 weiteren Autor:innen. Die Arbeit wurde bisher 3-mal zitiert (Crossref) und nennt 35 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY-NC-ND 4.0). Gefördert von: National Science and Technology Council.
Abstract (Originalsprache)
This study proposes a direct three‐phase four‐wire power flow method to accurately analyse the neutral line and multiple grounding characteristics. In particular, the proposed grounding impedance building‐based solution method was used to analyse the neutral grounding impedance in power flow studies based on the slack bus grounding impedance. The accuracy of the proposed method was verified using a neutral‐to‐earth voltage test system. IEEE 13‐bus and 123‐bus test systems were used to compare the advantages and disadvantages of the proposed method. Compared to the current injection full Newton and forward–backward sweep methods, the proposed method achieves a significant reduction in iteration numbers of up to 76.92% and 77.78%, respectively. For different grounding scenarios, stable convergence characteristics were exhibited by the proposed method after six to seven iterations.
Förderung
- National Science and Technology Council
Zitieren
APA
Yang, N., & Zeng, S. (2024). Three‐phase four‐wire power flow solution for multi‐grounded distribution networks with non‐bolted grounding. IET Generation, Transmission & Distribution, 18(23), 3914-3927. https://doi.org/10.1049/gtd2.13316
Vancouver
Yang N, Zeng S. Three‐phase four‐wire power flow solution for multi‐grounded distribution networks with non‐bolted grounding. IET Generation, Transmission & Distribution. 2024;18(23):3914-3927. doi:10.1049/gtd2.13316
BibTeX
@article{Yang2024,
author = {Yang, Nien‐Che and Zeng, Song‐Ting},
title = {Three‐phase four‐wire power flow solution for multi‐grounded distribution networks with non‐bolted grounding},
journal = {IET Generation, Transmission & Distribution},
year = {2024},
volume = {18},
number = {23},
pages = {3914--3927},
doi = {10.1049/gtd2.13316}
}