EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Security constrained optimal power shutoff for wildfire risk mitigation

Noah Rhodes, Carleton Coffrin, Line Roald

IET Generation, Transmission & Distribution · 2024-09 · 18 (18) · 2972-2986

DOI: 10.1049/gtd2.13246 ↗

Kurz gefasst

Fachartikel in der Zeitschrift IET Generation, Transmission & Distribution, online erschienen am 22.08.2024. Verfasst von Noah Rhodes und 2 weiteren Autor:innen. Die Arbeit wurde bisher 13-mal zitiert (Crossref) und nennt 71 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Advanced Scientific Computing Research, Division of Electrical, Communications and Cyber Systems.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Electric grid faults are increasingly the source of ignition for major wildfires. To reduce the likelihood of such ignitions in high risk situations, utilities use preemptive de‐energization of power lines, commonly referred to as Public Safety Power Shutoffs (PSPS). Besides raising challenging trade‐offs between power outages and wildfire safety, PSPS removes redundancy from the network at a time when component faults are likely to happen. This may leave the network particularly vulnerable to unexpected line faults that may occur while the PSPS is in place. Previous works have not explicitly considered the impacts of these outages. To address this gap, the Security Constrained Optimal Power Shutoff problem is proposed which uses post‐contingency security constraints to model the impact of unexpected line faults when planning a PSPS. This model enables, for the first time, the exploration of a wide range of trade‐offs between both wildfire risk and pre‐ and post‐contingency load shedding when designing PSPS plans, providing useful insights for utilities and policy makers considering different approaches to PSPS. The efficacy of the model is demonstrated using the EPRI 39‐bus system as a case study. The results highlight the potential risks of not considering security constraints when planning PSPS and show that incorporating security constraints into the PSPS design process improves the resilience of current PSPS plans.

Förderung

  • Advanced Scientific Computing Research
  • Division of Electrical, Communications and Cyber Systems

Zitieren

APA

Rhodes, N., Coffrin, C., & Roald, L. (2024). Security constrained optimal power shutoff for wildfire risk mitigation. IET Generation, Transmission & Distribution, 18(18), 2972-2986. https://doi.org/10.1049/gtd2.13246

Vancouver

Rhodes N, Coffrin C, Roald L. Security constrained optimal power shutoff for wildfire risk mitigation. IET Generation, Transmission & Distribution. 2024;18(18):2972-2986. doi:10.1049/gtd2.13246

BibTeX
@article{Rhodes2024,
  author = {Rhodes, Noah and Coffrin, Carleton and Roald, Line},
  title = {Security constrained optimal power shutoff for wildfire risk mitigation},
  journal = {IET Generation, Transmission & Distribution},
  year = {2024},
  volume = {18},
  number = {18},
  pages = {2972--2986},
  doi = {10.1049/gtd2.13246}
}
Kostenlos starten →