EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

New criteria for metal oxide surge arrester condition monitoring based on leakage current analysis: Considering non‐uniform pollution effect

Masume Khodsuz, Mohammad Hossein Teymourian, Seyyedmeysam Seyyedbarzegar

IET Generation, Transmission & Distribution · 2024-03 · 18 (5) · 1072-1089

DOI: 10.1049/gtd2.13123 ↗

Kurz gefasst

Fachartikel in der Zeitschrift IET Generation, Transmission & Distribution, online erschienen am 30.01.2024. Verfasst von Masume Khodsuz und 2 weiteren Autor:innen. Die Arbeit wurde bisher 20-mal zitiert (Crossref) und nennt 42 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

The role of surge arresters is vital in power systems' protection against transient overvoltages, which can arise due to occurrences like lightning strikes or switching operations. Based on the performance of the surge arrester, assessing its condition is an essential requirement for early detection of any damage or deterioration. This article proposes innovative criteria based on the surge arresters’ leakage current analysis for the classification of uniform and non‐uniform pollution levels. The leakage current signal of clean, uniform, and non‐uniform polluted surge arresters has been examined under different contamination levels, humidity, and non‐uniformity degrees. Based on the experimental results analysis, a new criterion has been proposed for assessing the surge arrester condition, which has resulted from the fifth and first‐order harmonics ratio of resistive leakage current. Analysis of the proposed criterion demonstrates that this index has a significant correlation to the pollution level. The proposed criterion ability has been established based on random forest, support vector machine, decision tree algorithm, and multi‐layer perceptron in Python language. The obtained criterion based on experimental data in different conditions has been employed for classifier training, which can be applied in the power network for better condition monitoring of surge arresters ensuring fast and accurate outcomes.

Zitieren

APA

Khodsuz, M., Teymourian, M. H., & Seyyedbarzegar, S. (2024). New criteria for metal oxide surge arrester condition monitoring based on leakage current analysis: Considering non‐uniform pollution effect. IET Generation, Transmission & Distribution, 18(5), 1072-1089. https://doi.org/10.1049/gtd2.13123

Vancouver

Khodsuz M, Teymourian MH, Seyyedbarzegar S. New criteria for metal oxide surge arrester condition monitoring based on leakage current analysis: Considering non‐uniform pollution effect. IET Generation, Transmission & Distribution. 2024;18(5):1072-1089. doi:10.1049/gtd2.13123

BibTeX
@article{Khodsuz2024,
  author = {Khodsuz, Masume and Teymourian, Mohammad Hossein and Seyyedbarzegar, Seyyedmeysam},
  title = {New criteria for metal oxide surge arrester condition monitoring based on leakage current analysis: Considering non‐uniform pollution effect},
  journal = {IET Generation, Transmission & Distribution},
  year = {2024},
  volume = {18},
  number = {5},
  pages = {1072--1089},
  doi = {10.1049/gtd2.13123}
}
Kostenlos starten →