EUVIMEDEUVIMED entdecken
Open Access · CC BY-NC-ND 4.0

Carbon‐Aware Optimal Dispatch for Hierarchical Distribution‐Microgrid Interconnected Systems With Three‐Port Converters: An MISOCP‐Based Approach

Jian Zhang, Xucheng Huang, Zhiwei Xu, Tao Zhang

IET Energy Systems Integration · 2026-01 · 8 (1)

DOI: 10.1049/esi2.70051 ↗

Kurz gefasst

Fachartikel in der Zeitschrift IET Energy Systems Integration, online erschienen am 06.08.2026. Verfasst von Jian Zhang und 3 weiteren Autor:innen. Die Arbeit nennt 26 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY-NC-ND 4.0). Gefördert von: National Natural Science Foundation of China.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Against the backdrop of carbon neutrality goals and new power system development, hierarchical distribution‐microgrid systems with three‐port converters (TPCs) have drawn extensive attention. However, existing research on such systems faces three challenges: the ambiguity of carbon potential (CP) at hybrid nodes within TPCs, the intractability of nonlinear nonconvex models and insufficient coordination between distribution networks and microgrids. To address these challenges, this paper proposes a real‐time carbon tracking and carbon‐aware optimal coordinated dispatch framework for hierarchical distribution‐microgrid systems with TPCs. First, by explicitly modelling the interport carbon emission flow interactions within TPCs, the CP of each hybrid node inside the TPCs is quantified, improving calculation accuracy by up to 89% over conventional empirical methods. Second, McCormick envelope relaxation and SOCP relaxation are introduced to convexify the bilinear carbon‐flow terms and power‐flow constraints, whereas binary variables are retained for ESS charging/discharging states. Accordingly, the proposed carbon‐aware optimal dispatch model is formulated as a mixed‐integer second‐order cone programming (MISOCP) problem, reducing the objective value by 4.29% compared with the nonconvex model while avoiding initial‐value sensitivity and local optima. Finally, a distribution‐microgrid coordinated low‐carbon dispatch strategy is proposed, which increases photovoltaic penetration to 84.11%, reduces curtailment to 11.89% and decreases carbon emission and electricity costs by 10.22% and 6.94%, respectively. These results provide a modelling and optimisation basis for low‐carbon operation of future hierarchical interconnected systems with high renewable penetration.

Förderung

  • National Natural Science Foundation of China

Zitieren

APA

Zhang, J., Huang, X., Xu, Z., & Zhang, T. (2026). Carbon‐Aware Optimal Dispatch for Hierarchical Distribution‐Microgrid Interconnected Systems With Three‐Port Converters: An MISOCP‐Based Approach. IET Energy Systems Integration, 8(1). https://doi.org/10.1049/esi2.70051

Vancouver

Zhang J, Huang X, Xu Z, Zhang T. Carbon‐Aware Optimal Dispatch for Hierarchical Distribution‐Microgrid Interconnected Systems With Three‐Port Converters: An MISOCP‐Based Approach. IET Energy Systems Integration. 2026;8(1). doi:10.1049/esi2.70051

BibTeX
@article{Zhang2026,
  author = {Zhang, Jian and Huang, Xucheng and Xu, Zhiwei and Zhang, Tao},
  title = {Carbon‐Aware Optimal Dispatch for Hierarchical Distribution‐Microgrid Interconnected Systems With Three‐Port Converters: An MISOCP‐Based Approach},
  journal = {IET Energy Systems Integration},
  year = {2026},
  volume = {8},
  number = {1},
  doi = {10.1049/esi2.70051}
}
Kostenlos starten →