EUVIMEDEUVIMED entdecken
Open Access · CC BY-NC-ND 4.0

Experimental study on temperature control of cable tunnel fire under the combined effect of fine water mist and mechanical ventilation

Hui Zhu, Jun Ji, Jingkai Nie, Yu Xia

Electrical Materials and Applications · 2024

DOI: 10.1049/ema3.70007 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Electrical Materials and Applications, 2024. Verfasst von Hui Zhu und 3 weiteren Autor:innen. Die Arbeit wurde bisher 2-mal zitiert (Crossref) und nennt 34 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY-NC-ND 4.0). Gefördert von: National Key Research and Development Program of China.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Electricity is an important energy supply for industry, and long‐distance transmission in China mainly relies on cable tunnels, while cable tunnel fires occur frequently. A 1:1 scale tunnel model with a length of 20 m, a width of 2.5 m, and a height of 2.5 m was used to conduct experimental research on the temperature field of the ceiling of a high‐voltage fine water mist suppression cable tunnel. The article conducted experimental research on parameters, such as nozzle pressure, nozzle position, and longitudinal ventilation speed in high‐pressure water mist systems using n‐hexane as the ignition source. The results indicate that the high‐pressure water mist system can effectively reduce the ceiling temperature during cable tunnel fires. When the mechanical smoke evacuation system is activated, it leads to a reduction in the overall temperature within the tunnel. When the mechanical smoke extraction system is integrated with the high‐pressure water mist system, therefore, it is feasible to integrate the high‐pressure water mist system with the mechanical smoke exhaust system in engineering applications.

Förderung

  • National Key Research and Development Program of China

Zitieren

APA

Zhu, H., Ji, J., Nie, J., & Xia, Y. (2024). Experimental study on temperature control of cable tunnel fire under the combined effect of fine water mist and mechanical ventilation. Electrical Materials and Applications. https://doi.org/10.1049/ema3.70007

Vancouver

Zhu H, Ji J, Nie J, Xia Y. Experimental study on temperature control of cable tunnel fire under the combined effect of fine water mist and mechanical ventilation. Electrical Materials and Applications. 2024. doi:10.1049/ema3.70007

BibTeX
@article{Zhu2024,
  author = {Zhu, Hui and Ji, Jun and Nie, Jingkai and Xia, Yu},
  title = {Experimental study on temperature control of cable tunnel fire under the combined effect of fine water mist and mechanical ventilation},
  journal = {Electrical Materials and Applications},
  year = {2024},
  doi = {10.1049/ema3.70007}
}
Kostenlos starten →