EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Implementing Geomagnetically Induced Currents Mitigation During the May 2024 “Gannon” G5 Storm: Research Informed Response by the New Zealand Power Network

D. H. Mac Manus, C. J. Rodger, A. Renton, V. Lo, J. Malone‐Leigh, T. Petersen, M. Copland, A. T. Hendry, M. A. Clilverd, G. S. Richardson

Space Weather · 2025-06 · 23 (6)

DOI: 10.1029/2025sw004388 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Space Weather, 2025-06. Verfasst von D. H. Mac Manus und 9 weiteren Autor:innen. Die Arbeit wurde bisher 17-mal zitiert (Crossref) und nennt 37 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Ministry of Business, Innovation and Employment.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

In early May 2024 6 Coronal Mass Ejections were launched toward the Earth in short succession. This triggered the G5 “Gannon” geomagnetic storm lasting from 17 UT on 10 May 2024 to 9 UT on 12 May 2024. Auroral displays were seen around the world including at lower latitudes than previous geomagnetic disturbances this century. Magnetic field variations measured at multiple sites in New Zealand exceeded values observed over the past 30 years. In 2022, following many years of industry‐research collaboration, an updated and enhanced “All of New Zealand” Geomagnetically Induced Current (GIC) mitigation strategy was developed. This strategy involves targeted line disconnections to reconfigure the network. The goal of this approach is to reduce GIC magnitudes and durations at the most at risk transformers, while still maintaining the continuous supply of power. Following training of control room staff, this strategy was declared operational in mid‐2023. Once disturbance levels reached the G5 threshold during the Gannon storm Transpower control room staff followed the planned procedure and implemented the mitigation strategy for the first time. There was no impact to New Zealand's electrical supply from this storm. GIC was measured at more than 70 transformers throughout the New Zealand power grid. Peak GICs observed after the mitigation strategy was in place reached 113 A at a transformer in the city of Dunedin. Without mitigation, modeling shows that a peak GIC of 200 A through the neutral would have occurred, exacerbated by the tripping of a transformer at a neighboring substation.

Förderung

  • Ministry of Business, Innovation and Employment

Zitieren

APA

Manus, D. H. M., Rodger, C. J., Renton, A., Lo, V., Malone‐Leigh, J., Petersen, T., Copland, M., Hendry, A. T., Clilverd, M. A., & Richardson, G. S. (2025). Implementing Geomagnetically Induced Currents Mitigation During the May 2024 “Gannon” G5 Storm: Research Informed Response by the New Zealand Power Network. Space Weather, 23(6). https://doi.org/10.1029/2025sw004388

Vancouver

Manus DHM, Rodger CJ, Renton A, Lo V, Malone‐Leigh J, Petersen T, et al. Implementing Geomagnetically Induced Currents Mitigation During the May 2024 “Gannon” G5 Storm: Research Informed Response by the New Zealand Power Network. Space Weather. 2025;23(6). doi:10.1029/2025sw004388

BibTeX
@article{Manus2025,
  author = {Manus, D. H. Mac and Rodger, C. J. and Renton, A. and Lo, V. and Malone‐Leigh, J. and Petersen, T. and Copland, M. and Hendry, A. T. and Clilverd, M. A. and Richardson, G. S.},
  title = {Implementing Geomagnetically Induced Currents Mitigation During the May 2024 “Gannon” G5 Storm: Research Informed Response by the New Zealand Power Network},
  journal = {Space Weather},
  year = {2025},
  volume = {23},
  number = {6},
  doi = {10.1029/2025sw004388}
}
Kostenlos starten →