A Resilient MEMS Sensor Array–AI System for DGA-Based Transformer Fault Monitoring in High-H 2 Environments
ACS Sensors · 24.10.2025 · 10 (10) · 8007-8015
DOI: 10.1021/acssensors.5c02569 ↗Kurz gefasst
Fachartikel in der Zeitschrift ACS Sensors, online erschienen am 01.10.2025. Verfasst von Ze Zhang und 8 weiteren Autor:innen. Beteiligte Einrichtung: State Key Laboratory for Manufacturing Systems Engineering, Xi'an Jiaotong University, Xi'an, Shaanxi 710049, P. R. China. Hauptthemen laut MEDLINE: Hydrogen, Micro-Electrical-Mechanical Systems. Die Arbeit wurde bisher 5-mal zitiert (Crossref) und nennt 26 Literaturangaben. Gefördert von: National Key Research and Development Program of China, International Joint Laboratory for MicroNano Manufacturing and Measurement Technologies.
Abstract (Originalsprache)
MOS gas sensors offer significant potential for real-time dissolved gas analysis (DGA) in power transformer monitoring. However, their performance is often degraded in high-hydrogen (H2) environments due to cross-interference, which impairs detection accuracy and limits practical deployment. To overcome these challenges, we propose a co-optimized sensing framework that integrates a MEMS-based hybrid sensor array with a CNN-LSTM-AM deep learning model. The hybrid array combines Pd-Au and MOS sensors to exploit their complementary gas-response behaviors, enabling reliable hydrocarbon detection even under H2 saturation. On the algorithmic side, a 1D convolutional neural network (CNN) extracts subtle gas features from saturated MOS signals, while the LSTM-based attention mechanism (LSTM-AM) compensates for Pd-Au sensor drift by learning temporal dependencies. To further enhance robustness, a smooth-label training method is introduced to reduce prediction instability during abrupt concentration transitions. Experimental results demonstrate that our framework achieves a mean squared error (MSE) of 0.0020 on a custom datset (D1), outperforming the UCI-TGS benchmark by 87.3% (MSE: 0.0157). Moreover, the smooth-label strategy reduces prediction variance by 50% compared to conventional labeling. This integrated hardware-algorithm system not only improves Pd-Au sensor performance and reduces training loss by half but also provides an accurate and robust solution for real-time DGA, contributing to enhanced diagnostic reliability in smart grid applications.
Schlagwörter
MeSH-Schlagwörter (MEDLINE)
Stichwörter der Autor:innen
Substanzen
Autor:innen und Institutionen
- State Key Laboratory for Manufacturing Systems Engineering, Xi'an Jiaotong University, Xi'an, Shaanxi 710049, P. R. China.
- Guangxi Power Grid Co Ltd Research Institute, China Southern Power Grid, Nanning, Guangxi 530023, P. R. China.
- Digital Grid Research Institute, China Southern Power Grid, Guangzhou, Guangdong 510700, P. R. China.
ORCID-Profile: Hairong Wang
Förderung
- National Key Research and Development Program of China
- International Joint Laboratory for MicroNano Manufacturing and Measurement Technologies
Zitieren
APA
Zhang, Z., Zhang, Y., Li, T., Zhang, C., Luo, Z., Luo, B., Tian, B., Zhao, Y., & Wang, H. (2025). A Resilient MEMS Sensor Array–AI System for DGA-Based Transformer Fault Monitoring in High-H 2 Environments. ACS Sensors, 10(10), 8007-8015. https://doi.org/10.1021/acssensors.5c02569
Vancouver
Zhang Z, Zhang Y, Li T, Zhang C, Luo Z, Luo B, et al. A Resilient MEMS Sensor Array–AI System for DGA-Based Transformer Fault Monitoring in High-H 2 Environments. ACS Sensors. 2025;10(10):8007-8015. doi:10.1021/acssensors.5c02569
BibTeX
@article{Zhang2025,
author = {Zhang, Ze and Zhang, Yining and Li, Tengfei and Zhang, Cheng and Luo, Zongchang and Luo, Bofeng and Tian, Bing and Zhao, Yulong and Wang, Hairong},
title = {A Resilient MEMS Sensor Array–AI System for DGA-Based Transformer Fault Monitoring in High-H 2 Environments},
journal = {ACS Sensors},
year = {2025},
volume = {10},
number = {10},
pages = {8007--8015},
doi = {10.1021/acssensors.5c02569}
}