EUVIMEDEUVIMED entdecken
Crossref

Charge-Driven Degradation of Residential Electret HVAC Filters under Wildfire Smoke Exposure

Shibo Wang iD, Qisheng Ou iD, Xiaoliang Wang, Zhengyuan Pan iD, Dongryul Park, Nikil Krishnakumar, Yipeng Hua, Francisco J Romay, Ryne A Juidici, Hooyoung Chung, Keonwang Lee, Jiarong Hong iD und 2 weitere

Environmental Science & Technology · 2026

DOI: 10.1021/acs.est.6c03046 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Environmental Science & Technology, 2026. Verfasst von Shibo Wang und 13 weiteren Autor:innen. Beteiligte Einrichtung: Center for Filtration Research, University of Minnesota Twin Cities, Minneapolis, Minnesota55455, United States. Hauptthemen laut MEDLINE: Smoke, Wildfires. Die Arbeit nennt 92 Literaturangaben.

AbstractSchlagwörterBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Wildfire smoke poses an increasingly significant threat to indoor air quality; however, the performance and durability of residential HVAC filters under sustained exposure to wildfire smoke remain poorly understood. Here, we show that wildfire smoke degrades electret filter performance through mechanisms fundamentally distinct from those captured by standard filtration tests. Combining laboratory-generated flaming and smoldering wood smoke, field sampling during prescribed burns, and controlled soot particle challenges, we demonstrate that filtration efficiency can collapse rapidly at particle loadings far below those associated with appreciable pressure drop increases. This behavior is driven primarily by soot-rich particles, which induce rapid and irreversible neutralization of electret charge rather than by progressive mechanical clogging or organic aerosol deposition alone. As a result, pressure-based filter-replacement criteria substantially overestimate usable filter lifetime during wildfire smoke events. Incorporating these experimentally constrained degradation pathways into a dynamic indoor air model reveals that effective filter lifetime during wildfire episodes can be reduced from months to days, even under moderate outdoor concentrations. Application to a regional wildfire event using U.S. EPA monitoring data further demonstrates that indoor protection varies significantly with building characteristics and ventilation strategies. These results identify soot-driven electret charge neutralization as a critical vulnerability of typical residential HVAC filters, reframing filtration performance under wildfire smoke exposure as primarily constrained by electret charge stability rather than pressure-drop-driven loading.

Schlagwörter

MeSH-Schlagwörter (MEDLINE)

SmokeWildfiresFiltrationAir Pollution, Indoor

Stichwörter der Autor:innen

Charge dissipationElectrostatic filtration, Smoke aerosolsFiltration agingIndoor air qualityParticle loading

Substanzen

Smoke

Autor:innen und Institutionen

  • Center for Filtration Research, University of Minnesota Twin Cities, Minneapolis, Minnesota55455, United States.
  • Desert Research Institute , Reno, Nevada89512, United States.
  • Air Science Laboratory, LG Electronics, Inc., Seoul08592, Republic of Korea.
  • Minnesota Robotics Institute and St. Anthony Falls Laboratory, University of Minnesota, Minneapolis, Minnesota55455, United States.

ORCID-Profile: Shibo Wang, Qisheng Ou, Zhengyuan Pan, Jiarong Hong

Zitieren

APA

Wang, S., Ou, Q., Wang, X., Pan, Z., Park, D., Krishnakumar, N., Hua, Y., Romay, F. J., Juidici, R. A., Chung, H., Lee, K., Hong, J., Park, H., & Pui, D. Y. H. (2026). Charge-Driven Degradation of Residential Electret HVAC Filters under Wildfire Smoke Exposure. Environmental Science & Technology. https://doi.org/10.1021/acs.est.6c03046

Vancouver

Wang S, Ou Q, Wang X, Pan Z, Park D, Krishnakumar N, et al. Charge-Driven Degradation of Residential Electret HVAC Filters under Wildfire Smoke Exposure. Environmental Science & Technology. 2026. doi:10.1021/acs.est.6c03046

BibTeX
@article{Wang2026,
  author = {Wang, Shibo and Ou, Qisheng and Wang, Xiaoliang and Pan, Zhengyuan and Park, Dongryul and Krishnakumar, Nikil and Hua, Yipeng and Romay, Francisco J and Juidici, Ryne A and Chung, Hooyoung and Lee, Keonwang and Hong, Jiarong and Park, Hyungho and Pui, David Y H},
  title = {Charge-Driven Degradation of Residential Electret HVAC Filters under Wildfire Smoke Exposure},
  journal = {Environmental Science & Technology},
  year = {2026},
  doi = {10.1021/acs.est.6c03046}
}
Kostenlos starten →