Natural ventilation performance for airborne diseases management in a deployable treatment facility
Infection Control & Hospital Epidemiology · 2026
DOI: 10.1017/ice.2026.10508 ↗Kurz gefasst
Fachartikel in der Zeitschrift Infection Control & Hospital Epidemiology, 2026. Verfasst von Luca Fontana und 7 weiteren Autor:innen. Beteiligte Einrichtung: Health Emergencies Programme, World Health Organization, Geneva, Switzerland. Hauptthemen laut MEDLINE: Ventilation, Air Microbiology, Cross Infection, Infection Control. Die Arbeit nennt 19 Literaturangaben. Gefördert von: World Health Organization.
Abstract (Originalsprache)
Objective
To assess whether wind-driven natural ventilation in the Infectious Diseases Treatment Module (IDTM) can achieve ventilation performance consistent with airborne precaution requirements [160 liters per second (L/s)] and to estimate associated pathogen-specific infection risks.
Methods
An experimental campaign of air velocity measurements and CO 2 decays were conducted to validate the developed computational fluid dynamics (CFD) model. The validated CFD model simulated wind-driven natural ventilation (1–4 m/s) for an L-shaped IDTM configuration under four structural scenarios defined by the presence or absence of patient porches and mosquito nets. Airborne infection risk was estimated using a Wells–Riley quanta-based model for seven representative airborne pathogens under short-duration healthcare worker exposure and prolonged patient co-exposure.
Results
Ventilation performance varied widely based on wind speed and structural configuration. Airflow ranged from 7 L/s in the most restricted configuration (porch and mosquito nets present at 1 m/s) to over 3,100 L/s when mosquito nets were removed at 4 m/s. When mapped to infection-risk estimates, ventilation rates at 160 L/s substantially reduced short-duration healthcare worker infection risk for all pathogens (≤1%), whereas prolonged co-exposure remained associated with high risk for high-emission pathogens despite high ventilation.
Conclusion
Under favorable wind conditions and optimized configurations, the IDTM can achieve ventilation rates consistent with the 160 L/s recommendation for airborne precautions. While this provides substantial protection for healthcare workers, individual-room isolation remains essential for patient management. Operationally, removing window-mounted nets is the most effective way to ensure safety targets are met; hybrid ventilation measures should be considered during low-wind conditions.
Schlagwörter
MeSH-Schlagwörter (MEDLINE)
Autor:innen und Institutionen
- Health Emergencies Programme, World Health Organization, Geneva, Switzerland.
- Department of Civil and Mechanical Engineering, Universita degli Studi di Cassino e del Lazio Meridionale, Italy.
- University Department of Anesthesiology and Intensive Care Medicine, University Hospital Tübingen, Germany.
ORCID-Profile: Luca Fontana, Gino Cortellessa, Giorgio Grossi, Anna Silenzi, Michele Di Marco, Robert Wunderlich
Förderung
- World Health Organization
Zitieren
APA
Fontana, L., Cortellessa, G., Grossi, G., Silenzi, A., Di Marco, M., Chaillon, A., Wunderlich, R., & Buonanno, G. (2026). Natural ventilation performance for airborne diseases management in a deployable treatment facility. Infection Control & Hospital Epidemiology. https://doi.org/10.1017/ice.2026.10508
Vancouver
Fontana L, Cortellessa G, Grossi G, Silenzi A, Di Marco M, Chaillon A, et al. Natural ventilation performance for airborne diseases management in a deployable treatment facility. Infection Control & Hospital Epidemiology. 2026. doi:10.1017/ice.2026.10508
BibTeX
@article{Fontana2026,
author = {Fontana, Luca and Cortellessa, Gino and Grossi, Giorgio and Silenzi, Anna and Di Marco, Michele and Chaillon, Antoine and Wunderlich, Robert and Buonanno, Giorgio},
title = {Natural ventilation performance for airborne diseases management in a deployable treatment facility},
journal = {Infection Control & Hospital Epidemiology},
year = {2026},
doi = {10.1017/ice.2026.10508}
}
EUVIMED