From ventilation compliance to performance: experimental and cfd analysis of supply–exhaust design for airborne infection isolation rooms
Results in Engineering · 2026-12 · 32 · 113038
DOI: 10.1016/j.rineng.2026.113038 ↗Kurz gefasst
Fachartikel in der Zeitschrift Results in Engineering, 2026-12. Verfasst von Ully Muzakir und 8 weiteren Autor:innen. Die Arbeit nennt 41 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY-NC-ND 4.0). Gefördert von: Universitas Syiah Kuala, Lembaga Pengelola Dana Pendidikan, Dana Ilmu Pengetahuan Indonesia.
Abstract (Originalsprache)
Airborne infection isolation rooms (AIIRs) are critical for preventing healthcare-associated transmission of infectious aerosols. Current guidelines prescribe minimum air change rates (≥12 ACH) and negative pressure, yet compliance does not necessarily ensure effective contaminant removal from the patient breathing zone. This study advances a performance-based evaluation of AIIR ventilation by examining how terminal-level design parameters govern airflow directionality and contaminant capture. A full-scale negative-pressure isolation room (15.2 m², 36.8 m³) maintained at −20 Pa was investigated through integrated experiments and computational fluid dynamics (CFD). Dry-ice smoke served as a tracer to visualize airflow pathways and exhaust-air (EA) suction behavior, while validated CFD simulations resolved velocity fields and recirculation structures across five supply–exhaust (SA–EA) configurations investigated by CFD, with the baseline configuration additionally validated experimentally through tracer visualization and anemometric measurements. Anemometer measurements at the baseline EA grille reveal a strikingly non-uniform vertical suction profile, with the face velocity decaying from 1.63 m/s at 110 cm above the floor to 0 m/s at 30 cm, a mean vertical gradient of ∼2.04 (m/s) per m , attributable to a geometric mismatch between the effective EA opening (0.036 m²) and the substantially larger EA face area (0.792 m²) , an opening-to-face area ratio of only ≈ 1 : 22. This near-floor low-velocity region (
Förderung
- Universitas Syiah Kuala
- Lembaga Pengelola Dana Pendidikan
- Dana Ilmu Pengetahuan Indonesia
Zitieren
APA
Muzakir, U., Razali, R., Irwansyah, I., Kurniawan, R., Mahlia, T. M. I., Muhammad, I., Ibrahim, I. B., Fuadi, Z., & Rizal, S. (2026). From ventilation compliance to performance: experimental and cfd analysis of supply–exhaust design for airborne infection isolation rooms. Results in Engineering, 32, 113038. https://doi.org/10.1016/j.rineng.2026.113038
Vancouver
Muzakir U, Razali R, Irwansyah I, Kurniawan R, Mahlia TMI, Muhammad I, et al. From ventilation compliance to performance: experimental and cfd analysis of supply–exhaust design for airborne infection isolation rooms. Results in Engineering. 2026;32:113038. doi:10.1016/j.rineng.2026.113038
BibTeX
@article{Muzakir2026,
author = {Muzakir, Ully and Razali, Razali and Irwansyah, Irwansyah and Kurniawan, Rudi and Mahlia, Teuku Meurah Indra and Muhammad, Ikramullah and Ibrahim, Israr B.M. and Fuadi, Zahrul and Rizal, Samsul},
title = {From ventilation compliance to performance: experimental and cfd analysis of supply–exhaust design for airborne infection isolation rooms},
journal = {Results in Engineering},
year = {2026},
volume = {32},
pages = {113038},
doi = {10.1016/j.rineng.2026.113038}
}
EUVIMED