Experimental investigation of a data-centre cooling system using a new single-phase immersion/liquid technique

Mohamad Hnayno, Ali Chehade, Henryk Klaba, Guillaume Polidori, Chadi Maalouf

Case Studies in Thermal Engineering · 2023-05 · 45 · 102925

DOI: 10.1016/j.csite.2023.102925 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Case Studies in Thermal Engineering, 2023-05. Verfasst von Mohamad Hnayno und 4 weiteren Autor:innen. Die Arbeit wurde bisher 78-mal zitiert (Crossref) und nennt 31 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

This paper presents an experimental investigation conducted on a new single-phase immersion/ liquid-cooling technique developed at the OVHcloud laboratory, combining a direct-to-chip water-cooling system with passive single-immersion cooling technology. The experimental setup tested the impact of three dielectric fluids (S5X, SmartCoolant and ThermaSafe R), the effect of the water circuit configuration, and the server power/profile. Results suggest that the system cooling demand depends on the fluid ’ s viscosity. As the viscosity increased from 4.6 to 9.8 mPa s, the cooling performance decreased by approximately 6%. Moreover, all the IT server profiles were validated at various water inlet temperatures and flow rates. The energy performance of the proposed technique and the liquid-cooling system previously used by OVHcloud was compared at a 600 kW data centre (DC). The proposed technique showed a reduction in the DC electrical power consumption by at least 20.7% compared to the liquid-cooling system. Finally, the cooling performance of the air-and liquid-cooled systems and the proposed solution was compared

Zitieren

APA

Hnayno, M., Chehade, A., Klaba, H., Polidori, G., & Maalouf, C. (2023). Experimental investigation of a data-centre cooling system using a new single-phase immersion/liquid technique. Case Studies in Thermal Engineering, 45, 102925. https://doi.org/10.1016/j.csite.2023.102925

Vancouver

Hnayno M, Chehade A, Klaba H, Polidori G, Maalouf C. Experimental investigation of a data-centre cooling system using a new single-phase immersion/liquid technique. Case Studies in Thermal Engineering. 2023;45:102925. doi:10.1016/j.csite.2023.102925

BibTeX
@article{Hnayno2023,
  author = {Hnayno, Mohamad and Chehade, Ali and Klaba, Henryk and Polidori, Guillaume and Maalouf, Chadi},
  title = {Experimental investigation of a data-centre cooling system using a new single-phase immersion/liquid technique},
  journal = {Case Studies in Thermal Engineering},
  year = {2023},
  volume = {45},
  pages = {102925},
  doi = {10.1016/j.csite.2023.102925}
}
Kostenlos starten →