Risk modeling for ASHRAE Standard 241-2023 — Control of infectious aerosols
Building and Environment · 2025-09 · 283 · 113318
DOI: 10.1016/j.buildenv.2025.113318 ↗Kurz gefasst
Fachartikel in der Zeitschrift Building and Environment, 2025-09. Verfasst von Benjamin Jones und 4 weiteren Autor:innen. Die Arbeit wurde bisher 14-mal zitiert (Crossref) und nennt 60 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).
Abstract (Originalsprache)
This paper describes the risk assessment modeling used to establish airflow requirements in ASHRAE Standard 241 (2023) – Control of Infectious Aerosols. The standard sets minimum equivalent clean airflow rates per person (ECA i ) to reduce long-range airborne disease transmission indoors during high infection risk periods. These requirements cover buildings and occupancy categories such as correctional facilities, schools, healthcare facilities, commercial spaces, and residences. The modeling employs the Wells–Riley infection risk model to estimate infection probability from inhaling aerosols over one hour. A probabilistic approach accounts for uncertainties, especially in key parameters like viral load, which can vary widely. Input parameters are based on SARS-CoV-2 data, as it was the primary motivation for the standard and provides higher-quality data. ECA i values are set to achieve a 0.1% hourly infection probability 96% of the time across different occupancy categories, resulting in ECA i values between 10-45 L s −1 per person. The standard focuses on long-range transmission and serves as one protective layer, complementing vaccines and personal protective equipment . Uncertainties are significant so the ECA i values represent informed estimates rather than precise values. This risk-based method provides a rational approach for setting minimum airflow requirements to mitigate airborne infection risks during outbreaks.
Zitieren
APA
Jones, B., Iddon, C., Zaatari, M., Wargocki, P., & Bruns, R. (2025). Risk modeling for ASHRAE Standard 241-2023 — Control of infectious aerosols. Building and Environment, 283, 113318. https://doi.org/10.1016/j.buildenv.2025.113318
Vancouver
Jones B, Iddon C, Zaatari M, Wargocki P, Bruns R. Risk modeling for ASHRAE Standard 241-2023 — Control of infectious aerosols. Building and Environment. 2025;283:113318. doi:10.1016/j.buildenv.2025.113318
BibTeX
@article{Jones2025,
author = {Jones, Benjamin and Iddon, Christopher and Zaatari, Marwa and Wargocki, Pawel and Bruns, Richard},
title = {Risk modeling for ASHRAE Standard 241-2023 — Control of infectious aerosols},
journal = {Building and Environment},
year = {2025},
volume = {283},
pages = {113318},
doi = {10.1016/j.buildenv.2025.113318}
}
EUVIMED