Post-occupancy evaluation on temporary negative pressure isolation wards with portable high-efficiency particulate air filter units used during the COVID-19 pandemic in South Korea

Se Jin Lee, Won Seok Lee, Joo Yeon Roh, Shin Hye Lee, Eun Seok Kim, Myoung Souk Yeo

American Journal of Infection Control · 2024

DOI: 10.1016/j.ajic.2024.08.025 ↗

Kurz gefasst

Fachartikel in der Zeitschrift American Journal of Infection Control, 2024. Verfasst von Se Jin Lee und 5 weiteren Autor:innen. Beteiligte Einrichtung: Department of Architecture and Architectural Engineering, Graduate School, Seoul National University, Seoul, South Korea. Hauptthemen laut MEDLINE: COVID-19, Air Filters, SARS-CoV-2. Die Arbeit wurde bisher 3-mal zitiert (Crossref) und nennt 37 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY-NC-ND 4.0). Gefördert von: Ministry of Health and Welfare.

AbstractSchlagwörterBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

BACKGROUND: During the COVID-19 pandemic, in South Korea, several inpatient wards were converted to temporary negative pressure isolation (TNPI) wards by using portable high-efficiency particulate air filter units (PHUs). This study proposes improvements to the TNPI ward to prepare for airborne infections. METHODS: Existing air-conditioning systems were investigated during the pandemic in 4 hospitals through a document review and field investigation with staff interviews. On-site experiments and measurements were conducted under vacant conditions. Differential pressure (∆P) between spaces was measured in all 4 hospitals, while tracer gas tests were carried out in 2 hospitals. RESULTS: The investigation revealed that thermal discomfort caused the existing systems remaining perpetually active. Additionally, the noise generated by the PHU caused an unexpected shutdown of that equipment. Furthermore, the ∆P of over -2.5 Pa was measured as a result of the operating status of equipment. These situations can cause duct backflow and gas diffusion through unsealed diffusers. Moreover, low airtightness of existing facilities can affect indoor environment, pressure difference, and gas diffusion. CONCLUSIONS: When using existing facilities as TNPI wards, the airtightness and existing systems should be considered. We concluded that it is important to increase the airtightness and seal unused diffusers in order to prevent cross-infection by unpredictable airflow.

Schlagwörter

MeSH-Schlagwörter (MEDLINE)

COVID-19Air FiltersSARS-CoV-2HumansRepublic of KoreaPatient IsolationAir ConditioningPandemics

Stichwörter der Autor:innen

Emergency conversionHVAC system operationPortable HEPA filterTemporary isolation room

Autor:innen und Institutionen

  • Department of Architecture and Architectural Engineering, Graduate School, Seoul National University, Seoul, South Korea.
  • Seoul Public Health Research Institute, Seoul Medical Center, Seoul, South Korea.
  • Department of Architecture and Architectural Engineering, College of Engineering, Seoul National University, Seoul, South Korea; Institute of Construction and Environmental Engineering (ICEE), Seoul National University,…

Förderung

  • Ministry of Health and Welfare

Zitieren

APA

Lee, S. J., Lee, W. S., Roh, J. Y., Lee, S. H., Kim, E. S., & Yeo, M. S. (2024). Post-occupancy evaluation on temporary negative pressure isolation wards with portable high-efficiency particulate air filter units used during the COVID-19 pandemic in South Korea. American Journal of Infection Control. https://doi.org/10.1016/j.ajic.2024.08.025

Vancouver

Lee SJ, Lee WS, Roh JY, Lee SH, Kim ES, Yeo MS. Post-occupancy evaluation on temporary negative pressure isolation wards with portable high-efficiency particulate air filter units used during the COVID-19 pandemic in South Korea. American Journal of Infection Control. 2024. doi:10.1016/j.ajic.2024.08.025

BibTeX
@article{Lee2024,
  author = {Lee, Se Jin and Lee, Won Seok and Roh, Joo Yeon and Lee, Shin Hye and Kim, Eun Seok and Yeo, Myoung Souk},
  title = {Post-occupancy evaluation on temporary negative pressure isolation wards with portable high-efficiency particulate air filter units used during the COVID-19 pandemic in South Korea},
  journal = {American Journal of Infection Control},
  year = {2024},
  doi = {10.1016/j.ajic.2024.08.025}
}
Kostenlos starten →