EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Two‐Layer Optimal Control Strategy of Thermal Power Unit Coupled With Hybrid Energy Storage System in Frequency Regulation

Zhiwei Xing, Lu Liang, Yunfeng Tian, Lei Liu, Chuan Zuo, Longfei Zhu, Zhan Li, Zhenyong Yang, Jingqiu Kang, Feng Hong

Energy Science & Engineering · 2026-04 · 14 (4) · 1965-1975

DOI: 10.1002/ese3.70457 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Energy Science & Engineering, online erschienen am 09.02.2026. Verfasst von Zhiwei Xing und 9 weiteren Autor:innen. Die Arbeit wurde bisher 2-mal zitiert (Crossref) und nennt 26 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

With the growing penetration of renewable energy, its intermittency and fluctuation have imposed increasingly stringent regulation requirements on thermal power units (TPU). To enhance the automatic generation control (AGC) response performance of TPU, this paper proposes an optimized two‐layer operation strategy integrating hybrid energy storage systems (HESS). Considering the significant regulation delay of TPU and the fast response characteristics of HESS, an upper‐layer control strategy based on nonlinear decomposition is developed for power allocation between the HESS and TPU. The lower‐layer control strategy optimized the power distribution and constraints of the flywheel energy storage system (FESS) and electrochemical energy storage system (BESS), taking into account the lifetime and state of charge (SOC) limitations of the BESS. Finally, the effectiveness of the proposed strategy is verified through simulation studies. The results show that when HESS assists the TPU in frequency regulation, the comprehensive performance index increased from 0.656 to 0.781, indicating a notable improvement in AGC performance. Compared with conventional HESS allocation methods, the proposed strategy reduced the power fluctuations of the TPU and enhanced the comprehensive regulation performance index by 6.4%.

Zitieren

APA

Xing, Z., Liang, L., Tian, Y., Liu, L., Zuo, C., Zhu, L., Li, Z., Yang, Z., Kang, J., & Hong, F. (2026). Two‐Layer Optimal Control Strategy of Thermal Power Unit Coupled With Hybrid Energy Storage System in Frequency Regulation. Energy Science & Engineering, 14(4), 1965-1975. https://doi.org/10.1002/ese3.70457

Vancouver

Xing Z, Liang L, Tian Y, Liu L, Zuo C, Zhu L, et al. Two‐Layer Optimal Control Strategy of Thermal Power Unit Coupled With Hybrid Energy Storage System in Frequency Regulation. Energy Science & Engineering. 2026;14(4):1965-1975. doi:10.1002/ese3.70457

BibTeX
@article{Xing2026,
  author = {Xing, Zhiwei and Liang, Lu and Tian, Yunfeng and Liu, Lei and Zuo, Chuan and Zhu, Longfei and Li, Zhan and Yang, Zhenyong and Kang, Jingqiu and Hong, Feng},
  title = {Two‐Layer Optimal Control Strategy of Thermal Power Unit Coupled With Hybrid Energy Storage System in Frequency Regulation},
  journal = {Energy Science & Engineering},
  year = {2026},
  volume = {14},
  number = {4},
  pages = {1965--1975},
  doi = {10.1002/ese3.70457}
}