Design and Optimization of Cleanroom Systems From an Energy Perspective

Seyed Mojtaba Dehghan, Akbar Amirian, Ahmad Hajinezhad, Seyed Farhan Moosavian, Reza Fattahi

Energy Science & Engineering · 2026-01 · 14 (1) · 428-443

DOI: 10.1002/ese3.70365 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Energy Science & Engineering, online erschienen am 18.11.2025. Verfasst von Seyed Mojtaba Dehghan und 4 weiteren Autor:innen. Die Arbeit wurde bisher 4-mal zitiert (Crossref) und nennt 21 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

In this study, a novel optimization approach is proposed for cleanroom ventilation systems with a specific focus on plastic injection molding machines used in pharmaceutical manufacturing. The research uses MATLAB‐based numerical modeling to analyze the effects of air changes per hour (ACH), fresh air intake percentage, and internal heat generation on energy consumption. Three different climatic conditions—winter, mild spring, and summer—are examined to determine the optimal operating parameters for heating, ventilation, and air conditioning (HVAC) systems. The results indicate that adjusting ACH and fresh air intake percentages dynamically based on seasonal variations reduces heating and cooling loads significantly. In winter conditions, a 50% fresh air intake at an ACH of 50 minimizes heating demand by utilizing internally generated heat. In summer, increasing fresh air intake optimally lowers cooling demand by exhausting excess equipment‐generated heat. Moreover, implementing intelligent control strategies based on real‐time temperature monitoring reduces unnecessary energy consumption while maintaining required cleanroom standards. These findings demonstrate that strategic HVAC adjustments can enhance energy efficiency, reducing overall heating and cooling loads without compromising cleanroom air quality and regulatory compliance.

Zitieren

APA

Dehghan, S. M., Amirian, A., Hajinezhad, A., Moosavian, S. F., & Fattahi, R. (2026). Design and Optimization of Cleanroom Systems From an Energy Perspective. Energy Science & Engineering, 14(1), 428-443. https://doi.org/10.1002/ese3.70365

Vancouver

Dehghan SM, Amirian A, Hajinezhad A, Moosavian SF, Fattahi R. Design and Optimization of Cleanroom Systems From an Energy Perspective. Energy Science & Engineering. 2026;14(1):428-443. doi:10.1002/ese3.70365

BibTeX
@article{Dehghan2026,
  author = {Dehghan, Seyed Mojtaba and Amirian, Akbar and Hajinezhad, Ahmad and Moosavian, Seyed Farhan and Fattahi, Reza},
  title = {Design and Optimization of Cleanroom Systems From an Energy Perspective},
  journal = {Energy Science & Engineering},
  year = {2026},
  volume = {14},
  number = {1},
  pages = {428--443},
  doi = {10.1002/ese3.70365}
}
Kostenlos starten →