Pressure Rises Due to Arc under Insulating Oil in Closed Vessel—Pressure Fluctuation of Depth Direction in Oil
Electrical Engineering in Japan · 2018-01 · 202 (2) · 43-53
DOI: 10.1002/eej.23042 ↗Kurz gefasst
Fachartikel in der Zeitschrift Electrical Engineering in Japan, online erschienen am 20.10.2017. Verfasst von TOMO TADOKORO und 4 weiteren Autor:innen. Die Arbeit wurde bisher 28-mal zitiert (Crossref) und nennt 11 Literaturangaben.
Abstract (Originalsprache)
When a fault arc occurs in oil‐filled electric equipment, it generates a flammable gas and a dynamic pressure rise. In this study, the pressure rises due to the arc are measured in a closed vessel containing air and oil for different arc depths. The pressure rises in air and oil with different depth are measured under experimental conditions involving an arc current 6.6 kA, an arc duration of 100 ms. Experimental results show that the frequency of pressure fluctuation varies with the depth of the arc. Our approximate calculation of the pressure fluctuation with consideration of the oil flux is consistent with the experimental results.
Zitieren
APA
TADOKORO, T., KOTARI, M., OHTAKA, T., IWATA, M., & AMAKAWA, T. (2018). Pressure Rises Due to Arc under Insulating Oil in Closed Vessel—Pressure Fluctuation of Depth Direction in Oil. Electrical Engineering in Japan, 202(2), 43-53. https://doi.org/10.1002/eej.23042
Vancouver
TADOKORO T, KOTARI M, OHTAKA T, IWATA M, AMAKAWA T. Pressure Rises Due to Arc under Insulating Oil in Closed Vessel—Pressure Fluctuation of Depth Direction in Oil. Electrical Engineering in Japan. 2018;202(2):43-53. doi:10.1002/eej.23042
BibTeX
@article{TADOKORO2018,
author = {TADOKORO, TOMO and KOTARI, MASASHI and OHTAKA, TOSHIYA and IWATA, MIKIMASA and AMAKAWA, TADASHI},
title = {Pressure Rises Due to Arc under Insulating Oil in Closed Vessel—Pressure Fluctuation of Depth Direction in Oil},
journal = {Electrical Engineering in Japan},
year = {2018},
volume = {202},
number = {2},
pages = {43--53},
doi = {10.1002/eej.23042}
}