EUVIMEDEUVIMED entdecken
Crossref

A Fault‐Tolerant Control Method for Grid‐Connected MMC Employing Compound Mutual Inductance Charge Channel

Fei Yao, Chaojie Guo, Lizhi Sun

International Journal of Circuit Theory and Applications · 29.07.2026

DOI: 10.1002/cta.70581 ↗

Kurz gefasst

Fachartikel in der Zeitschrift International Journal of Circuit Theory and Applications, online erschienen am 29.07.2026. Verfasst von Fei Yao und 2 weiteren Autor:innen. Die Arbeit nennt 20 Literaturangaben. Gefördert von: Fundamental Research Funds for the Central Universities.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

For the long‐distance grid connection of offshore wind farms, high‐voltage direct current (HVDC) transmission systems based on modular multilevel converters (MMC) are now the predominant technical solution. Although the MMC offers high voltage output capability, its reliance on a large number of continuously operating IGBTs renders it prone to faults. To address open‐circuit faults in IGBTs within MMC submodules (SMs) and ensure grid‐connection reliability, this paper employs a compound mutual inductance charge channel and a modulated wave reconstruction method after MMC faults. The fault‐tolerant control mechanism of the proposed method under typical fault conditions is thoroughly analyzed, which proves that the capacitor in the faulted submodule can be discharged by using this method. Additionally, this method operates independently of voltage and current sensor data, enabling sensorless operation. The results show that after two types of faults occur and the proposed fault‐tolerant method is employed, the voltage fluctuation rate of the submodule capacitors transitions from a divergent state to a stable fluctuation, with the fluctuation rate not exceeding 4.53%, and the THD of the output current is reduced by 93.82% and 98.12%, respectively. Comprehensive simulation and experimental studies substantiate the proposed method, confirming its feasibility and effectiveness.

Förderung

  • Fundamental Research Funds for the Central Universities

Zitieren

APA

Yao, F., Guo, C., & Sun, L. (2026). A Fault‐Tolerant Control Method for Grid‐Connected MMC Employing Compound Mutual Inductance Charge Channel. International Journal of Circuit Theory and Applications. https://doi.org/10.1002/cta.70581

Vancouver

Yao F, Guo C, Sun L. A Fault‐Tolerant Control Method for Grid‐Connected MMC Employing Compound Mutual Inductance Charge Channel. International Journal of Circuit Theory and Applications. 2026. doi:10.1002/cta.70581

BibTeX
@article{Yao2026,
  author = {Yao, Fei and Guo, Chaojie and Sun, Lizhi},
  title = {A Fault‐Tolerant Control Method for Grid‐Connected MMC Employing Compound Mutual Inductance Charge Channel},
  journal = {International Journal of Circuit Theory and Applications},
  year = {2026},
  doi = {10.1002/cta.70581}
}
Kostenlos starten →