EUVIMEDEUVIMED entdecken
Crossref

A PLL Strategy With Fractional‐Order Lead Correction Enhances the Weak Grid Adaptability of LCL Grid‐Connected Inverter

Yanwei Jiang, Letian Lin, Lian Luo, Xujian Shu, Jingjing Yang

International Journal of Circuit Theory and Applications · 05.03.2026

DOI: 10.1002/cta.70383 ↗

Kurz gefasst

Fachartikel in der Zeitschrift International Journal of Circuit Theory and Applications, online erschienen am 05.03.2026. Verfasst von Yanwei Jiang und 4 weiteren Autor:innen. Die Arbeit nennt 28 Literaturangaben. Gefördert von: National Natural Science Foundation of China.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

As the impedance of the power grid increases, the power grid state will exhibit weak grid characteristics. The grid‐connected inverter is indispensable as the connection unit between the large power grid and the distributed generation system. However, there is an interaction between the grid‐connected inverter and the grid impedance, which can easily induce the broadband oscillation of the grid‐connected system. To solve this problem, a phase‐locked loop (PLL) control strategy based on fractional‐order lead correction is proposed, which further improves the phase margin and dynamic response performance of the system by flexibly adjusting the differential and integral orders. The simulation and a 1.5 kW experimental prototype show that the system can still operate stably under weak grid conditions with a short‐circuit ratio (SCR) of 1.7, proving the feasibility of the proposed control strategy.

Förderung

  • National Natural Science Foundation of China

Zitieren

APA

Jiang, Y., Lin, L., Luo, L., Shu, X., & Yang, J. (2026). A PLL Strategy With Fractional‐Order Lead Correction Enhances the Weak Grid Adaptability of LCL Grid‐Connected Inverter. International Journal of Circuit Theory and Applications. https://doi.org/10.1002/cta.70383

Vancouver

Jiang Y, Lin L, Luo L, Shu X, Yang J. A PLL Strategy With Fractional‐Order Lead Correction Enhances the Weak Grid Adaptability of LCL Grid‐Connected Inverter. International Journal of Circuit Theory and Applications. 2026. doi:10.1002/cta.70383

BibTeX
@article{Jiang2026,
  author = {Jiang, Yanwei and Lin, Letian and Luo, Lian and Shu, Xujian and Yang, Jingjing},
  title = {A PLL Strategy With Fractional‐Order Lead Correction Enhances the Weak Grid Adaptability of LCL Grid‐Connected Inverter},
  journal = {International Journal of Circuit Theory and Applications},
  year = {2026},
  doi = {10.1002/cta.70383}
}
Kostenlos starten →